| Installation method | Minimum cover | Notes |
|---|---|---|
| Direct-burial UF cable, no conduit | 24 inches | The default for unprotected cable |
| PVC (nonmetallic) conduit | 18 inches | Most common residential method |
| Rigid metal conduit (RMC or IMC) | 6 inches | Steel provides the mechanical protection |
| 120V branch circuit, 20 amps or less, GFCI-protected | 12 inches | The shallow allowance most shed and post-light runs use |
| Low-voltage landscape lighting (30V or less) | 6 inches | Transformer-fed lighting wire only |
Now two things trip homeowners up. First, the measurement: 24 inches of cover means the top of the cable sits 24 inches down, so the trench itself is going to be deeper. Second is the location changes the number: direct-burial cable under a driveway or parking area needs 24 inches of cover regardless of circuit size, because vehicles drive over it constantly.